NVD Vulnerability Detail
Search Exploit, PoC
CVE-2017-7905
Summary

A Weak Cryptography for Passwords issue was discovered in General Electric (GE) Multilin SR 750 Feeder Protection Relay, firmware versions prior to Version 7.47; SR 760 Feeder Protection Relay, firmware versions prior to Version 7.47; SR 469 Motor Protection Relay, firmware versions prior to Version 5.23; SR 489 Generator Protection Relay, firmware versions prior to Version 4.06; SR 745 Transformer Protection Relay, firmware versions prior to Version 5.23; SR 369 Motor Protection Relay, all firmware versions; Multilin Universal Relay, firmware Version 6.0 and prior versions; and Multilin URplus (D90, C90, B95), all versions. Ciphertext versions of user passwords were created with a non-random initialization vector leaving them susceptible to dictionary attacks. Ciphertext of user passwords can be obtained from the front LCD panel of affected products and through issued Modbus commands.

Publication Date June 30, 2017, 12:29 p.m.
Registration Date Jan. 26, 2021, 1:29 p.m.
Last Update Nov. 21, 2024, 12:32 p.m.
CVSS3.0 : CRITICAL
スコア 9.8
Vector CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H
攻撃元区分(AV) ネットワーク
攻撃条件の複雑さ(AC)
攻撃に必要な特権レベル(PR) 不要
利用者の関与(UI) 不要
影響の想定範囲(S) 変更なし
機密性への影響(C)
完全性への影響(I)
可用性への影響(A)
CVSS2.0 : MEDIUM
Score 5.0
Vector AV:N/AC:L/Au:N/C:P/I:N/A:N
攻撃元区分(AV) ネットワーク
攻撃条件の複雑さ(AC)
攻撃前の認証要否(Au) 不要
機密性への影響(C)
完全性への影響(I) なし
可用性への影響(A) なし
Get all privileges. いいえ
Get user privileges いいえ
Get other privileges いいえ
User operation required いいえ
Affected software configurations
Configuration1 or higher or less more than less than
cpe:2.3:o:ge:multilin_sr_750_feeder_protection_relay_firmware:*:*:*:*:*:*:*:* 5.02
execution environment
1 cpe:2.3:h:ge:multilin_sr_750_feeder_protection_relay:-:*:*:*:*:*:*:*
Configuration2 or higher or less more than less than
cpe:2.3:o:ge:multilin_sr_760_feeder_protection_relay_firmware:*:*:*:*:*:*:*:* 5.02
execution environment
1 cpe:2.3:h:ge:multilin_sr_760_feeder_protection_relay:-:*:*:*:*:*:*:*
Configuration3 or higher or less more than less than
cpe:2.3:o:ge:multilin_sr_469_motor_protection_relay_firmware:*:*:*:*:*:*:*:* 2.90
execution environment
1 cpe:2.3:h:ge:multilin_sr_469_motor_protection_relay:-:*:*:*:*:*:*:*
Configuration4 or higher or less more than less than
cpe:2.3:o:ge:multilin_sr_489_generator_protection_relay_firmware:*:*:*:*:*:*:*:* 1.53
execution environment
1 cpe:2.3:h:ge:multilin_sr_489_generator_protection_relay:-:*:*:*:*:*:*:*
Configuration5 or higher or less more than less than
cpe:2.3:o:ge:multilin_sr_745_transformer_protection_relay_firmware:*:*:*:*:*:*:*:* 2.85
execution environment
1 cpe:2.3:h:ge:multilin_sr_745_transformer_protection_relay:-:*:*:*:*:*:*:*
Configuration6 or higher or less more than less than
cpe:2.3:o:ge:multilin_sr_369_motor_protection_relay_firmware:-:*:*:*:*:*:*:*
execution environment
1 cpe:2.3:h:ge:multilin_sr_369_motor_protection_relay:-:*:*:*:*:*:*:*
Configuration7 or higher or less more than less than
cpe:2.3:o:ge:multilin_universal_relay_firmware:*:*:*:*:*:*:*:* 6.0
execution environment
1 cpe:2.3:h:ge:multilin_universal_relay:-:*:*:*:*:*:*:*
Configuration8 or higher or less more than less than
cpe:2.3:o:ge:multilin_urplus_d90_firmware:-:*:*:*:*:*:*:*
execution environment
1 cpe:2.3:h:ge:multilin_urplus_d90:-:*:*:*:*:*:*:*
Configuration9 or higher or less more than less than
cpe:2.3:o:ge:multilin_urplus_c90_firmware:-:*:*:*:*:*:*:*
execution environment
1 cpe:2.3:h:ge:multilin_urplus_c90:-:*:*:*:*:*:*:*
Configuration10 or higher or less more than less than
cpe:2.3:o:ge:multilin_urplus_b95_firmware:-:*:*:*:*:*:*:*
execution environment
1 cpe:2.3:h:ge:multilin_urplus_b95:-:*:*:*:*:*:*:*
Related information, measures and tools
Common Vulnerabilities List

JVN Vulnerability Information
複数の General Electric 製品における暗号に関する脆弱性
Title 複数の General Electric 製品における暗号に関する脆弱性
Summary

複数の General Electric (GE) 製品には、暗号に関する脆弱性が存在します。

Possible impacts 情報を取得される、情報を改ざんされる、およびサービス運用妨害 (DoS) 状態にされる可能性があります。
Solution

ベンダ情報および参考情報を参照して適切な対策を実施してください。

Publication Date April 27, 2017, midnight
Registration Date Aug. 3, 2017, 4:52 p.m.
Last Update Aug. 3, 2017, 4:52 p.m.
Affected System
General Electric Company
SR 369 Motor Protection Relay ファームウェア すべてのバージョン
SR 469 Motor Protection Relay ファームウェア 5.23 未満
SR 489 Generator Protection Relay ファームウェア 4.06 未満
SR 745 Transformer Protection Relay ファームウェア 5.23 未満
SR 750 Feeder Protection Relay ファームウェア 7.47 未満
SR 760 Feeder Protection Relay ファームウェア 7.47 未満
Universal Relay ファームウェア 6.0 およびそれ以前
URplus B95 すべてのバージョン
URplus C90 すべてのバージョン
URplus D90 すべてのバージョン
CVE (情報セキュリティ 共通脆弱性識別子)
CWE (共通脆弱性タイプ一覧)
ベンダー情報
その他
Change Log
No Changed Details Date of change
0 [2017年08月03日]
  掲載
Feb. 17, 2018, 10:37 a.m.